KSh 64,370(KSh 74,669 Incl VAT)
Device Type: 2kVA / 2000W True Online Double-Conversion Rack Mount UPS (Maxion Series)
Model / SKU: NPS-AC02R72IWB
Brand: Norden
Capacity: 2000 VA / 2000 W
Input: Phase: Single Phase with Ground; Normal Voltage: 208/220/230/240 VAC; Input Voltage Range: 110–300 VAC (176–264 VAC @ 100% load; 276–300 VAC @ 50% load); Frequency Range: 50/60 Hz Auto Sensing ±5 Hz; Input Power Factor: ≥0.99 @ Nominal Voltage (100% load); Input Connection: IEC C14
Output: Output Voltage: 208/220/230/240 VAC (Selectable); Output Power Factor: 1.0 (Unity); Voltage Regulation: ±1%; Frequency Range (Battery Mode): 50/60 Hz ±0.1 Hz; Current Crest Ratio: 3:1; Harmonic Distortion (THDv): ≤2% (Linear Load) / ≤5% (Non-Linear Load); Transfer Time: AC to DC: Zero (0 ms) / Inverter to Bypass: 4 ms; Waveform: Pure Sinewave; Output Connections: 8 × IEC C13
Efficiency: AC Mode: Up to 96%
Battery: System Voltage: 72 VDC; Configuration: 6 × 12V/9Ah VRLA (Internal Battery Configuration). Note: The base model NPS-AC02R72IWB is specified as "Without Battery" in some regional listings. The equivalent model with an internal battery is NPS-AC02R72I (or NPS-AC02T72I for the tower version). Please confirm the exact battery configuration with your supplier.
Typical Recharging Time: 4 hours to recover to 90% capacity
Charging Current (Max): 1A (Internal) / 1–12A (Settable, External Battery Configuration)
Display & Alarms: LCD Display (Input/Output Voltage, Battery Capacity, Load Percentage, Operating Mode, Fault Information)
Communication: RS232 (Standard); USB, IoT Card, and SNMP Card (Optional)
Protection: Overload, Short Circuit, Voltage Fluctuation; Built-in EMI Filter and Surge Protection; Emergency Power Off (EPO) Function; Cold Start Function
Physical: Form Factor: 2U Rack Mount (Tower Convertible); Dimensions (W×D×H): 480 × 440 × 180 mm (2U Rack); IP Rating: IP20
Environmental: Operating Temperature: 0°C to 40°C; Storage Temperature: -20°C to 70°C; Humidity: 0–95% RH @ 0–40°C (Non-Condensing); Noise Level: <50 dB @ 1 Meter
Standards & Certifications: Safety: CE; IEC/EN 62040-1; EMC: IEC/EN 62040-2; IEC 61000-4-2; IEC 61000-4-3; IEC 61000-4-4; IEC 61000-4-5; IEC 61000-4-6; IEC 61000-4-8; IEC 61000-4-11
Key Specs: Norden NPS-AC02R72IWB Maxion Series 2kVA/2000W True Online Double-Conversion Rack Mount UPS, Unity Power Factor (1.0), Pure Sinewave Output, Zero Transfer Time (AC to DC), 8× IEC C13 Outlets, 96% Efficiency, Wide Input Range (110–300VAC), LCD Display, SNMP/USB/RS232/IoT Optional, EPO Function, 2U Rack Mount (Tower Convertible), 72V Battery System
Usage: Rack Servers, Network Cabinets, Telecommunication Equipment, Data Centers, Industrial Control Panels, Security & Surveillance Systems, and Mission-Critical IT Infrastructure