Device Type: 3000VA / 1800W Line-Interactive UPS with AVR (Automatic Voltage Regulation)
Model / SKU: NPS-3000WB
Brand: Norden
Capacity: 3000 VA / 1800 W
Input: Normal Voltage: 220/230/240 VAC; Voltage Range: 162–290 VAC; Frequency Range: 50/60 Hz (auto-sensing)
Output: AC Voltage Regulation (Battery Mode): ±10%; Frequency Range (Battery Mode): 50/60 Hz ±1 Hz; Transfer Time: 2–6 ms typical, 10 ms max.; Waveform (Battery Mode): Simulated Sinewave
Output Sockets: 6 × IEC C13 outlets (as specified in product name)
Battery: Battery Voltage: 48 VDC; Battery Type & Number: 12 V / 9 Ah × 4; Typical Recharge Time: 6–8 hours to recover to 90% capacity
Note: The base model NPS-3000WB is specified as "Without Battery" — the internal batteries are not included. The equivalent model with an internal battery is CN3000N. The NPS-3000WB-LU variant includes LCD display and USB port but is also without battery.
Display: LED Display (LED version): AC Mode, Battery Mode, Overload, Fault; LCD Display (LCD version): AC Mode, Battery Mode, Load Level, Battery Level, Input Voltage, Output Voltage, Overload, Fault, and Battery Low
Communication: Optional USB or RS232 Port (Supports Windows 7/8/10, Linux, Unix, and MAC); Optional RJ11/RJ45 protection
Protection: Short Circuit, Overload, Overcharge, and Over-Discharge Protection
Alarms: Battery Mode: Sounding every 10 seconds; Low Battery: Sounding every second; Overload: Sounding every 0.5 second; Battery Replacement Alarm: Sounding every 2 seconds; Fault: Continuously sounding
Physical: Dimensions (W×D×H): 433 × 144 × 207 mm; Net Weight: Approx. 23 kg
Environmental: Humidity: 0–90% RH @ 0–40°C (Non-Condensing); Noise Level: Less than 55 dB
Certifications: Safety: CE, IEC/EN 62040-1, IEC/EN 60950-1; EMC: IEC/EN 62040-2, IEC 61000-4-2/3/4/5/6/8; Performance: IEC/EN 62040-3
Key Features: Line-Interactive Topology, Simulated Sinewave Output, Boost and Buck AVR (one boost and one buck control), Microprocessor Control with Internal Self-Diagnostic Technology, Auto Restart While AC is Recovering, Cold Start Function, Off-Mode Charging, Fast Intelligent Battery Recharge Function, Optional Generator Compatible
Key Specs: Norden NPS-3000WB 3000VA/1800W Line-Interactive UPS, 6× IEC C13 Outlets, AVR Stabilization (162–290V), Simulated Sinewave Output, 2–6 ms Transfer Time, 48V Battery System (4× 12V/9Ah), Optional USB/RS232 Monitoring, Overload/Short Circuit Protection, CE & IEC Certified
Usage: Business and Critical Power Applications, Servers, Telecommunication Hardware, Networking Devices, Small to Medium Enterprise Equipment, and Essential Power Protection for Commercial Installations