Device Type: Sealed Maintenance-Free (SMF) VRLA / AGM Rechargeable Battery
Part Number/SKU: AL065001-EX (also referenced as 12AL065)
Brand: Amaron Quanta™
Nominal Voltage: 12V DC
Rated Capacity: 65Ah @ C20 rate (20-hour, 1.75VPC, 27°C)
Battery Technology: Valve-Regulated Lead-Acid (VRLA), AGM (Absorbent Glass Mat), Maintenance-Free
Physical Specifications:- Dimensions (L × W × H): 351 × 167 × 175 mm (±2mm)
- Weight: 19.20 kg (±5%) / Approx. 20 kg filled
- Terminal Type: M6 × 20 mm Bolted
- Case Material: Standard PPCP (12AL065); FR Version UL 94-V0 (12ALZ065)
Performance & Reliability:- Internal Resistance: Approx. 9.4 mΩ (fully charged, 27°C)
- Short Circuit Current: 1382 A (per IEC)
- Cycle Life: Approximately 1,000 cycles at 50% Depth of Discharge (DOD)
- Self-Discharge Rate: <4% per month at 27°C(Solwave listing cites <3% per month at 25°C)
Capacity at Different Discharge Rates (27°C):- 10hr rate: 55.90 Ah (5.59 A, 10.5V/battery)
- 5hr rate: 51.40 Ah (10.29 A, 10.2V/battery)
- 1hr rate: 36.30 Ah (36.3 A, 9.6V/battery)
Capacity vs. Temperature (at C20 hr rate):- 40°C: 110%
- 27°C: 100%
- 0°C: 80%
- -15°C: 60%
Charging Parameters:- Standby Use (Float) @ 27°C: 13.5V/battery; Max Current 25% of rated capacity; Temp. Compensation ±18mV/battery/°C
- Cyclic Use (Boost) @ 27°C: 13.8V/battery; Max Current 25% of rated capacity; Temp. Compensation ±30mV/battery/°C
- Recommended Charging Voltage (Solwave listing): 14.4V – 14.9V
Operating Temperature Range: -20°C to +60°C (50–60°C for shorter duration)
Nominal Operating Temperature: 27°C ± 3°C
Compliance: JIS C8702/1998 (Part 1, 2 & 3) with latest amendments
Warranty: 24 Months (Manufacturer's Warranty Against Manufacturing Defects)
Key Specs: Amaron Quanta AL065001-EX (12AL065), 12V 65Ah Sealed Maintenance-Free VRLA/AGM Battery, Non-Spillable Sealed Design, 10-Year Design Float Life, Low Self-Discharge (<4%/Month at 27°C), ~1,000 Cycles at 50% DOD, Internal Resistance ~9.4mΩ, Short Circuit Current 1382A, M6 Bolted Terminals, PPCP Case, 351×167×175mm, 19.2kg, -20°C to +60°C Operating Range, JIS C8702 Compliant, 24-Month Warranty
Usage: Uninterruptible Power Supplies (UPS), Solar Energy Storage, Inverters, Telecommunication Equipment, Fire Alarm & Security Systems, Emergency Backup Systems, Medical Equipment, and Other Critical Standby Power Applications